K082464 Ferraz Shawmut - Fuse

Category: Fuses & Circuit Protection

Specifications: 250V, 300A

K082464 Ferraz Shawmut Fuse

We beat competitor's price with faster delivery.

For 6 pieces or more, submit your inquiry here, email to sales@uscomponent.com or call 1-281-968-0718

K082464 Description

The K082464 from Mersen is a semiconductor fuse with a 250 V / 300 A rating. It protects power semiconductors such as diodes, thyristors and IGBTs from short-circuit damage in drives, rectifiers and UPS systems.

Need the K082464? USComponent stocks and sources power modules for repair shops, OEMs and maintenance teams worldwide. Request a quote and we'll confirm availability and lead time. Always compare against the datasheet before ordering.

Summary of Features

Mersen (Ferraz Shawmut) K082464 is a Protistor BS88-4 semiconductor protection fuse, size 2x36x27 (double body), 300 A, 250 VAC, class gR, without trip indicator (designation URGH 236/300; catalog number BS236UH25V300).

Target Applications

Ferraz Shawmut K082464 is used for protection of power semiconductors (diodes, thyristors, IGBT modules) in rectifiers, AC drives, soft starters, UPS systems and other power electronic equipment with AC supply up to 250 V.

Key Specifications

Mersen (Ferraz Shawmut) K082464 is a Protistor BS88-4 semiconductor protection fuse, size 2x36x27 (double body), 300 A, 250 VAC, class gR, without trip indicator (designation URGH 236/300; catalog number BS236UH25V300). Source: Mersen Protistor BS88-4 semiconductor fuses 36x27 / 2x36x27, 250 VAC datasheet (SCAC206-207).

ParameterValue
Catalog numberBS236UH25V300
Reference numberK082464
DesignationURGH 236/300
StandardBS 88-4 / IEC 60269-4, VDE 636-23
Rated voltage250 VAC
Rated current300 A
Utilization classgR
Size2x36x27 (double body)
Breaking capacity100 kA at 250 V
Pre-arcing I²t (1 ms)7700 A²s
Total clearing I²t at 250 V31800 A²s
Watts loss at 0.8 IN / IN21.6 W / 43.2 W
Trip indicatorwithout trip indicator
Minimum operating voltage for trip indicator20 V
Weight (approx.)290 g