K080946 Ferraz Shawmut - Fuse
K080946 Description
Mersen makes the K080946, a 250 V, 75 A semiconductor fuse. It protects power semiconductors such as diodes, thyristors and IGBTs from short-circuit damage in drives, rectifiers and UPS systems.
Request a quote for the K080946 and our team will get back to you with price, quantity available and lead time. We ship worldwide. As with any power device, please check the manufacturer's datasheet to confirm it matches your design.
Summary of Features
Mersen (Ferraz Shawmut) K080946 is a Protistor BS88-4 semiconductor protection fuse, size 36x27, 75 A, 250 VAC, class gR, without trip indicator (designation URGG 36/75; catalog number BS36UG25V75).
Target Applications
Ferraz Shawmut K080946 is used for protection of power semiconductors (diodes, thyristors, IGBT modules) in rectifiers, AC drives, soft starters, UPS systems and other power electronic equipment with AC supply up to 250 V.
Key Specifications
Mersen (Ferraz Shawmut) K080946 is a Protistor BS88-4 semiconductor protection fuse, size 36x27, 75 A, 250 VAC, class gR, without trip indicator (designation URGG 36/75; catalog number BS36UG25V75). Source: Mersen Protistor BS88-4 semiconductor fuses 36x27 / 2x36x27, 250 VAC datasheet (SCAC206-207).
| Parameter | Value |
|---|---|
| Catalog number | BS36UG25V75 |
| Reference number | K080946 |
| Designation | URGG 36/75 |
| Standard | BS 88-4 / IEC 60269-4, VDE 636-23 |
| Rated voltage | 250 VAC |
| Rated current | 75 A |
| Utilization class | gR |
| Size | 36x27 |
| Breaking capacity | 100 kA at 250 V |
| Pre-arcing I²t (1 ms) | 330 A²s |
| Total clearing I²t at 250 V | 1380 A²s |
| Watts loss at 0.8 IN / IN | 6.3 W / 12.6 W |
| Trip indicator | without trip indicator |
| Minimum operating voltage for trip indicator | 20 V |
| Weight (approx.) | 170 g |
Technical document (PDF) | Request a quote for K080946 (reply within 24 hours)