DLD2450 Crydom - Relays

Category: Solid State Relays & I/O Modules

Specifications: 240(V) / 50(A)

DLD2450 Crydom Relays

We beat competitor's price with faster delivery.

For 6 pieces or more, submit your inquiry here, email to sales@uscomponent.com or call 1-281-968-0718

DLD2450 Description

The Crydom DLD2450 is a solid state relay, rated for 240 V and 50 A. It is widely used for heater control, motor switching, lighting and process equipment where mechanical contacts would wear out.

USComponent has sourced power semiconductors for maintenance teams and OEMs since 2001. For price and availability of the DLD2450, send us a request for quote. Please confirm the specifications against the manufacturer's datasheet before purchase.

Summary of Features

Crydom DLD2450 is a 50 A time-delay solid state relay (DLD Series, 48-280 VAC), zero-crossing output, DC control 3.5-15 VDC, turn-on delay set by an external resistor (1.6 s (0 Ohm) to 133 s (1.0 MOhm)).

Target Applications

Crydom DLD2450 is used for time-delayed switching of heaters, motors, lamps and other loads in industrial control, HVAC and process equipment.

Key Specifications

Crydom DLD2450 is a 50 A time-delay solid state relay (DLD Series, 48-280 VAC), zero-crossing output, DC control 3.5-15 VDC, turn-on delay set by an external resistor (1.6 s (0 Ohm) to 133 s (1.0 MOhm)). Source: Crydom DSD / DLD Series datasheet. Values at 25°C unless noted.

ParameterValue
Output
Operating voltage (47-63 Hz)48-280 Vrms
Maximum load current50 Arms
Minimum load current0.04 Arms
Transient overvoltage600 Vpk
Maximum surge current (16.6 ms)625 Apk
Maximum on-state voltage drop @ rated current1.6 Vpk
Thermal resistance junction to case (Rjc)0.63 °C/W
Maximum I²t for fusing (8.3 ms)1620 A²s
Maximum off-state leakage @ rated voltage10 mArms
Minimum off-state dv/dt500 V/µs
Input
Control voltage range3.5-15 VDC
Turn-on / turn-off voltage3.5 / 1.0 VDC
Typical input current3.4 mA @ 5 VDC, 11.4 mA @ 15 VDC
Nominal input impedance1500 Ohm
Typical turn-on delay (external resistor 0 / 10 k / 100 k / 470 k / 1 M Ohm)1.6 / 3.1 / 15 / 64 / 133 s
Maximum turn-off time1/2 cycle
Maximum reset time100 µs
General
Dielectric strength, input/output/base4000 Vrms
Ambient operating temperature-30 to 80°C

Technical document (PDF)  |  Request a quote for DLD2450 (reply within 24 hours)

Related Part Numbers

DLD2425
240V / 25A
DLD2410
240V / 10A
DLM02