CWA48125 Crydom - Relays
CWA48125 Description
Crydom makes the CWA48125, a solid state relay. Typical uses include temperature control of heaters, packaging and plastics machinery, and general industrial load switching.
USComponent has been supplying power semiconductors since 2001, including discontinued and hard-to-find part numbers. Send us an RFQ for the CWA48125 and we will reply with price, condition and lead time. Please check the manufacturer's datasheet to confirm ratings, package and pin-out before you order.
Summary of Features
Crydom CWA48125 is a 125 A panel-mount solid state relay, CW48 Series (48-660 VAC), SCR output, AC control (90-280 VAC), zero voltage turn-on, with LED status indicator and IP20 touch-safe cover.
Target Applications
Crydom CWA48125 is used for switching AC loads in industrial heating and temperature control (ovens, furnaces, plastic molding and extrusion machines), packaging and food processing equipment, lighting control, HVAC systems and industrial automation.
Key Specifications
Crydom CWA48125 is a 125 A panel-mount solid state relay, CW48 Series (48-660 VAC), SCR output, AC control (90-280 VAC), zero voltage turn-on, with LED status indicator and IP20 touch-safe cover. Source: Crydom CW48 Series datasheet (FDE-07-01 Rev. A). Values at 25°C unless noted.
| Parameter | Value |
|---|---|
| Output | |
| Operating voltage (47-440 Hz) | 48-660 Vrms |
| Maximum load current | 125 Arms |
| Transient overvoltage | 1200 Vpk |
| Minimum load current | 250 mArms |
| Maximum 1-cycle surge current (50/60 Hz) | 1900/2000 Apk |
| Maximum on-state voltage drop @ rated current | 1.25 Vpk |
| Maximum off-state leakage @ rated voltage | 1 mArms |
| Minimum off-state dv/dt | 500 V/µs |
| Maximum I²t for fusing, 1/2 cycle (50/60 Hz) | 18000/16600 A²s |
| Thermal resistance junction to case (Rjc) | 0.11 °C/W |
| Motor rating (UL 508 / IEC 60947) | 3 HP @ 120 VAC, 7.5 HP @ 240 VAC, 15 HP @ 480 VAC |
| Switching type | zero voltage turn-on |
| Input | |
| Control voltage range | 90-280 VAC |
| Minimum turn-on voltage | 90 VAC |
| Must turn-off voltage | 10 VAC |
| Input current | 6-10 mA |
| Maximum turn-on / turn-off time | 20 ms / 30 ms |
| General | |
| Dielectric strength, input/output/base | 4000 Vrms |
| Ambient operating temperature | -40 to 80°C |
| LED input status indicator | Green |
| Weight (typical) | 2.88 oz (81.53 g) |
Technical document (PDF) | Request a quote for CWA48125 (reply within 24 hours)