CMA24125-10 Crydom - Relays
CMA24125-10 Description
Rated at 240 V and 125 A, the Crydom CMA24125-10 is a solid state relay. It is widely used for heater control, motor switching, lighting and process equipment where mechanical contacts would wear out.
USComponent has sourced power semiconductors for maintenance teams and OEMs since 2001. For price and availability of the CMA24125-10, send us a request for quote. Please confirm the specifications against the manufacturer's datasheet before purchase.
Summary of Features
Crydom CMA24125-10 is a 125 A panel-mount solid state relay, CMD/CMA24 Series (24-280 VAC), SCR output, AC control (90-140 Vrms), random turn-on, LED input indicator, IP20 touch-safe housing with box-clamp terminals.
Target Applications
Crydom CMA24125-10 is used for switching AC loads in industrial heating and temperature control (ovens, furnaces, plastic molding and extrusion machines), packaging and food processing equipment, lighting control, HVAC systems and industrial automation.
Key Specifications
Crydom CMA24125-10 is a 125 A panel-mount solid state relay, CMD/CMA24 Series (24-280 VAC), SCR output, AC control (90-140 Vrms), random turn-on, LED input indicator, IP20 touch-safe housing with box-clamp terminals. Source: Crydom CMD/CMA24 Series datasheet (Rev. 113011). Values at 25°C unless noted.
| Parameter | Value |
|---|---|
| Output | |
| Operating voltage (47-63 Hz) | 24-280 Vrms |
| Maximum load current | 125 Arms |
| Transient overvoltage | 600 Vpk |
| Maximum 1 cycle surge current (50/60 Hz) | 1670/1750 Apk |
| Maximum on-state voltage drop @ rated current | 1.6 Vpk |
| Maximum off-state leakage @ rated voltage | 10 mArms |
| Minimum off-state dv/dt | 500 V/µs |
| Thermal resistance junction to case (Rjc) | 0.22 °C/W |
| Maximum I²t for fusing (1/2 cycle, 50/60 Hz) | 13950/12709 A²s |
| Switching type | random turn-on |
| Input | |
| Control voltage range | 90-140 Vrms |
| Minimum turn-on / turn-off voltage | 90 Vrms / 10 Vrms |
| Typical input current | 15 mA @ 120 Vrms |
| Maximum turn-on / turn-off time | 10 ms / 40 ms |
| General | |
| Dielectric strength, input/output/base | 4000 Vrms |
| Ambient operating temperature | -40 to 80°C |
| Weight (typical) | 3.0 oz (86.5 g) |
Technical document (PDF) | Request a quote for CMA24125-10 (reply within 24 hours)