X081003 Ferraz Shawmut - Fuse

Category: Fuses & Circuit Protection

Specifications: 250V, 150A

X081003 Ferraz Shawmut Fuse

Availability and lead time are confirmed in our quote.

  • ✓ Quote within 24 hours
  • ✓ Original manufacturer parts, inspected before shipping
  • ✓ Credit cards and NET terms accepted

Or email sales@uscomponent.com or call 1-281-968-0718.

X081003 Description

The Mersen X081003 is a semiconductor fuse, rated for 250 V and 150 A. Its job is to clear faults fast enough to save expensive semiconductors in drives, UPS units and DC supplies.

Request a quote for the X081003 and our team will get back to you with price, quantity available and lead time. We ship worldwide. As with any power device, please check the manufacturer's datasheet to confirm it matches your design.

Summary of Features

Mersen (Ferraz Shawmut) X081003 is a Protistor BS88-4 semiconductor protection fuse, size 36x27, 150 A, 250 VAC, class gR, with separate trip indicator (designation URGG 36P150; catalog number BS36UG25V150P).

Target Applications

Ferraz Shawmut X081003 is used for protection of power semiconductors (diodes, thyristors, IGBT modules) in rectifiers, AC drives, soft starters, UPS systems and other power electronic equipment with AC supply up to 250 V.

Key Specifications

Mersen (Ferraz Shawmut) X081003 is a Protistor BS88-4 semiconductor protection fuse, size 36x27, 150 A, 250 VAC, class gR, with separate trip indicator (designation URGG 36P150; catalog number BS36UG25V150P). Source: Mersen Protistor BS88-4 semiconductor fuses 36x27 / 2x36x27, 250 VAC datasheet (SCAC206-207).

ParameterValue
Catalog numberBS36UG25V150P
Reference numberX081003
DesignationURGG 36P150
StandardBS 88-4 / IEC 60269-4, VDE 636-23
Rated voltage250 VAC
Rated current150 A
Utilization classgR
Size36x27
Breaking capacity100 kA at 250 V
Pre-arcing I²t (1 ms)1930 A²s
Total clearing I²t at 250 V7950 A²s
Watts loss at 0.8 IN / IN10.8 W / 21.6 W
Trip indicatorwith separate trip indicator
Matching microswitchMC 36 GR 2.5 N, ref. Y310005
Minimum operating voltage for trip indicator20 V
Weight (approx.)185 g

Technical document (PDF)  |  Request a quote for X081003 (reply within 24 hours)

Related Part Numbers

X081854
1500V, 1500A
X076173
1500V, 750A
X098805X076150
1500V, 125A
X076104
1500V, 400A
X075506
250V, 500A