HD60125-10 Crydom - Relays

Also written as: HD6012510

Category: Solid State Relays & I/O Modules

Specifications: 480(V) / 125(A)

HD60125-10 Crydom Relays

Availability and lead time are confirmed in our quote.

  • ✓ Quote within 24 hours
  • ✓ Original manufacturer parts, inspected before shipping
  • ✓ Credit cards and NET terms accepted

Or email sales@uscomponent.com or call 1-281-968-0718.

HD60125-10 Description

Crydom makes the HD60125-10, a solid state relay. Solid state relays like this switch heaters, motors, lamps and other loads quietly and without contact wear.

USComponent has been supplying power semiconductors since 2001, including discontinued and hard-to-find part numbers. Send us an RFQ for the HD60125-10 and we will reply with price, condition and lead time. Please check the manufacturer's datasheet to confirm ratings, package and pin-out before you order.

Summary of Features

Crydom HD60125-10 is a 125 A panel-mount solid state relay, HA/HD60 Series (48-660 VAC), SCR output, DC control, instantaneous (random) turn-on.

Target Applications

Crydom HD60125-10 is used for switching AC loads in industrial heating and temperature control (ovens, furnaces, plastic molding and extrusion machines), packaging and food processing equipment, lighting control, HVAC systems and industrial automation.

Key Specifications

Crydom HD60125-10 is a 125 A panel-mount solid state relay, HA/HD60 Series (48-660 VAC), SCR output, DC control, instantaneous (random) turn-on. Source: Crydom HA/HD60 Series datasheet. Values at 25°C unless noted.

ParameterValue
Output
Operating voltage (47-440 Hz)48-660 Vrms
Maximum load current125 Arms
Transient overvoltage1200 Vpk
Minimum load current150 mArms
Maximum 1-cycle surge current (50/60 Hz)1670/1750 Apk
Maximum on-state voltage drop @ rated current1.15 Vrms
Maximum off-state leakage @ rated voltage1.0 mArms
Minimum off-state dv/dt500 V/µs
Maximum I²t for fusing, 1/2 cycle (50/60 Hz)13950/12709 A²s
Thermal resistance junction to case (Rjc)0.22 °C/W
Switching typeinstantaneous (random) turn-on
Input
Control voltage range4-32 VDC
Minimum turn-on voltage4.0 VDC
Must turn-off voltage1.0 VDC
Input current7-12 mA
Maximum turn-on / turn-off time1/2 cycle / 1/2 cycle
General
Dielectric strength, input/output/base4000 Vrms
Ambient operating temperature-40 to 80°C
Weight (typical)2.6 oz (74.9 g)

Technical document (PDF)  |  Request a quote for HD60125-10 (reply within 24 hours)

Related Part Numbers

HD48125-10
480(V) / 125(A)
HD48110-10
480(V) / 110(A)
HD6090-10
600(V) / 90(A)
HD6050-10
600(V) / 25(A)
HD6025-10
600(V) / 25(A)
HD4890-10
48(V) / 90(A)
HD-4850-10
480(V) / 50(A)
HD4825-10
480(V) / 25(A)
HD60125
600(V) / 125(A)
HD6025
600(V) / 25(A)
HD6050
600(V) / 50(A)
HD6090
600(V) / 90(A)
HD61602RHHD49723HD49716HD4890-G
480(V) / 90(A)