DR-OAC Crydom - Relays
Also written as: DROAC
DR-OAC Description
The Crydom DR-OAC is a solid state relay, rated for 240 V and 5 A. It is widely used for heater control, motor switching, lighting and process equipment where mechanical contacts would wear out.
USComponent has sourced power semiconductors for maintenance teams and OEMs since 2001. For price and availability of the DR-OAC, send us a request for quote. Please confirm the specifications against the manufacturer's datasheet before purchase.
Summary of Features
Crydom DR-OAC is a DIN-rail single-point AC output module (35 mm DIN), logic input 5-24 VDC (3.7-32 VDC), 5.0 Arms output, 4 kV optical isolation, LED indicator.
Target Applications
Crydom DR-OAC is used for interfacing field devices (switches, sensors, motor starters, valves, lamps) with PLCs, microprocessor and computer control systems.
Key Specifications
Crydom DR-OAC is a DIN-rail single-point AC output module (35 mm DIN), logic input 5-24 VDC (3.7-32 VDC), 5.0 Arms output, 4 kV optical isolation, LED indicator. Source: Crydom DR Output Modules datasheet. Values at 25°C unless noted.
| Parameter | Value |
|---|---|
| Input | |
| Logic voltage (nominal / range) | 5-24 VDC (3.7-32 VDC) |
| Drop-out voltage | 1.0 VDC |
| Maximum input current | 18 mA |
| Output | |
| Line voltage (nominal / range) | 240 VAC (12-280 VAC) |
| Maximum off-state voltage | 600 Vpk |
| Maximum off-state leakage | 0.1 mArms |
| Maximum rated on-state current | 5.0 Arms |
| Minimum on-state current | 50 mArms |
| Maximum surge current | 250 Apk |
| On-state voltage drop | 1.6 V |
| HP rating | 1/2 HP |
| Static off-state dv/dt | 200 V/µs |
| Recommended fuse | 5 A |
| Maximum turn-on / turn-off time | 8.33 ms / 8.33 ms |
| General | |
| Input/output isolation | 4000 V |
| Operating temperature | -30 to 80°C |
Technical document (PDF) | Request a quote for DR-OAC (reply within 24 hours)